Skip to main content

OMR card - IN.13

OMR card - IN.13

IN.13 - 2x Universal counter

Universal counter plug-in card for the OMR 700 is fully isolated from the internal bus.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.

  • 2x Counter / frequency / time
  • UP/DW, IRC
  • range: < 1 MHz
  • sensor power supply 5/24 VDC
Input
*
Number of inputs
2 vstupy
UQC
Input
on contact, TTL, NPN/PNP, Line
5/10/12/24/30 V
Input frequency
0,1 Hz…1 MHz
Calibration coefficient
ano
Preset
ano
Input filter
100/200/500 µs
1/2/5/10/20/50/100/200/500 ms
1/2/5/10/20/50 s
1/2/5/10 min
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
±0,05 % of range
(frequency)
Overload capacity
2x; 10x (t < 30 ms)
Functions
Tare designed to reset display on non-zero input signal
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Power supply
Power supply
interní sběrnice 3,3 VDC,24 VDC
Current draw
< 2,5 W
Operating conditions
Connection
connector terminal board, cable section < 1,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and inputs
Insulation resistance
for polution degree II, measuring cat. III.
input, bus 300 V (ZI), 150 V (Di)*
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
Mechanical properties
Dimensions
65 x 98 mm
Installation
plug-in card
Images
Connection