Skip to main content

OMR card - OUT.1

OMR card - OUT.1

OUT.1 - 4x Relay output

Relay output plug-in card for the OMR 700 is fully isolated from the internal bus.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.
 

  • 4x Output with an SPDT relay
  • ON / OFF
Instrument accuracy and functionality
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Comparators
Type
Digital, menu adjustable, contact connect. < 10 ms
Mode
Hysteresis switch. point, hysteresis band "Mez ± 1/2 Hys." and time (0 ... 99.9 s) determ. switching delay
Ready output switching signals perfect status
Error output switching signals error status
Rec output is active while recording data
Output
4x relay, switch-over contact (250 VAC/50 VDC, 3 A)
Power supply
Power supply
interní sběrnice 5 VDC,24 VDC
Current draw
< 0,75 W
Operating conditions
Connection
connector terminal board, cable section < 2,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and outputs
2,5 kVAC within 1 min. between output
Insulation resistance
for polution degree II, measuring cat. III.
output, bus 300 V (ZI), 150 V (Di)*
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
Mechanical properties
Dimensions
65 x 98 mm
Installation
plug-in card
Images
Připojení